ProSoft Technology MVI56-AFC User Manual

Page 198

Advertising
background image

MVI56-AFC Backplane Communication

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 198 of 316

ProSoft Technology, Inc.

February 25, 2011

Description
These two function codes allow you to write data from the controller to the vast

address space of the AFC module for its consumption. The two functions are

designed to access the two separate holding register banks by assigning unique

function codes for each type of access. These two function codes are tabulated

below in this section.
This block performs an arbitrary data transfer between the PLC and the AFC

data table. Any data transfer that can be performed with a Modbus command to

either AFC slave through any of the module’s ports may be implemented using

the gateway.
Any data words not relevant to the command are ignored upon output (to the

AFC) and zero upon input (from the AFC). Gateway data transfer may be

controlled through the use of the "ignore output" bit of the block ID. The "skip

input" bit has no function and is ignored.

MB Gateway Write: OFB

MB Gateway Write: IFB

Element

Attribute

Element

Attribute

0

Block ID - Function Code &

Length

0

Block ID - Function Code &

Status

1

Modbus Register Address

1

Reserved

2

Write Number of Registers (m)

2

Reserved

3

Data (write) Element 1

3

Reserved

4

Data (write) Element 2

4

Reserved

5

Data (write) Element 3

5

Reserved

………………………..

Reserved

………………………..

Reserved

n

Data (write) Element (n-2)

n

Reserved

Note: The number of registers for a Gateway Write Function block must not exceed two less than
the data block length declared in the OFB ID.

Modbus Gateway Write Function Codes

Function Code

To Write to Register Bank

To address AFC Slave

20

Holding

Primary

21

Holding

Virtual

Advertising
This manual is related to the following products: