ProSoft Technology MVI56-AFC User Manual

Page 220

Advertising
background image

MVI56-AFC Sample Logic

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 220 of 316

ProSoft Technology, Inc.

February 25, 2011

12.3 ControlLogix Sample Logic Details

This section shows how you can extract important information from the sample

logic without requiring you to know the details of how the sample logic actually

works. For most applications it will be enough to refer only to the controller tags

in order to perform the tasks.

12.3.1 Enable/Disable Status

Each meter run will only perform flow calculation while it is enabled. However,

you cannot change a meter type, product group or units while the meter is

enabled. In order to accomplish this, you have to disable the meter, change

meter type, product or units and then enable the meter again. The meters can be

enabled or disabled from logic or AFC Manager.
The logic constantly reads each meter enable/disable status from the MVI56-

AFC.
Refer to AFC56.EnableStatus data structure for each meter status. Each variable

should be interpreted as:
AFC56.EnableStatus.Meterx = 0 => Meter x is Disabled
AFC56.EnableStatus.Meterx = 1 => Meter x is Enabled

In the previous example, Meter 1 and Meter 2 are enabled. All other meters are

disabled.

12.3.2 Disable Meter

Each meter can be disabled through logic. Refer to the AFC56.DisableMeter data

structure. Toggle each AFC56.DisableMeter.Meterx controller tag in order to

command the meter to be enabled.