Error Recovery
During a session, the AFC maintains sufficient context information to accept not

only the next expected Modbus transaction of the sequence but also a repeat of

the previous one, except for the Commit Session and Abandon Session actions

(see below). This is to permit simple repetition of a transaction that has

succeeded from the point of view of the AFC but has failed from that of the host,

which would occur when the Modbus response transmitted by the AFC is not

received by the host. (If the host uses Collapsed Acknowledgement, it must take

care to set the acknowledgement bit correctly in a repeated Fetch.) Other than in

such a case, any Modbus transaction that does not comply strictly with the

conditions and sequencing described above is rejected with a Modbus exception

code (typically code 2, Illegal Address, if not addressing LDW offset 0, otherwise

code 3, Illegal Data).
Because both the Commit Session and the Abandon Session actions close the

session, there is afterwards no session context to allow recognition of a repeated
Commit or Abandon. In this case, a repeated Commit elicits a Modbus exception

of 3, Illegal Data, and a repeated Abandon is accepted without error regardless

of its Session ID.

Session Timeout
All transactions of a session must succeed frequently enough so that the duration

between successful transactions does not exceed the session timeout. Each

successful transaction restarts the timeout. If the timeout expires, the session is

automatically abandoned. Other Modbus activity, unrelated to the log-download

session, is not considered, and its only effect upon the timeout would be delays

of session transactions imposed by bandwidth usage.