ProSoft Technology MVI56-AFC User Manual

Page 297

Advertising
background image

MVI56-AFC ♦ ControlLogix Platform

Reference

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 297 of 316

February 25, 2011

Bit

Parameter

Value

bit 7

Modbus mode

0: RTU mode
1: ASCII mode

bit 8

Modbus orientation

0: slave
1: master (permitted only for last port)

bit 9

Primary slave
accessibility (not

meaningful for master

port)

0: primary slave accessible through this port
1: primary slave not accessible (not permitted for Port 1)

bit 10

Swap Modbus bytes

bit 11

Swap Modbus words

bit 12

Disable pass-thru (not meaningful for master port)

bits 13 to 15

[reserved]


A change in configuration takes effect after transmission of the response to the

Modbus command that causes the change; the response is sent using the old

configuration, but subsequent Modbus commands to the reconfigured port must

use the new one. Writing a baud code of 0 means that the current configuration

is not to be changed, and all other items are ignored. Default values are 6 for the

bitmap (9600,N,8,1,RTU,slave,primary,noswap,passthru) and 0 for the timeout

and both delays. The message transmission procedure is:
 Raise RTS.
 If TmoC is zero ignore CTS, else wait up to TmoC clock ticks for CTS.
 Delay for Dly1 clock ticks.
 Transmit message.
 Delay for Dly0 clock ticks.
 Drop RTS.

Advertising
This manual is related to the following products: