ProSoft Technology MVI56-AFC User Manual

Page 246

Advertising
background image

MVI56-AFC Sample Logic

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 246 of 316

ProSoft Technology, Inc.

February 25, 2011

4 In the sample ladder logic, configure each Modbus Gateway Block using the

following controller tags:

Parameter

Controller Tag

Values

Enable

Transaction

AFC56.ModbusGateway.Command

[0].Config.Enable

0 = The module will ignore this request
1 = The module will process this request.

Start Register

AFC56.ModbusGateway.Command

[0].Config.StartRegister

Start register in the Modbus Slave to be

written or read from

Register Count

AFC56.ModbusGateway.Command

[0].Config RegisterCount

Number of words to be written or read
between the module and the processor.

Maximum of 200 words is supported per

command.

Function Type

AFC56.ModbusGateway.Command

[0].Config.FunctionType_Write

0 = Read from MVI56-AFC
1 = Write to MVI56-AFC

Register Type

AFC56.ModbusGateway.Command

[0].Config.RegisterType_Input

0 = Holding Register
1 = Input Register

Slave Type

AFC56.ModbusGateway.Command

[0].Config.SlaveType_Virtual

0 = Primary Slave
1 = Virtual Slave

Note: It is strongly suggested that you first configure all parameters having the Enable bit set to 0.
After the configuration is finished than the Enable bit can be set to 1.

Example 1 - Modbus Gateway Function
In order to write 200 words from the processor to the Primary Modbus Slave

starting at holding register address 2000, the AFC56.Modbus.Gateway[0] block

should be configured as follows:

1 Refer to the AFC56.ModbusGateway.Command[x].WriteData or

AFC56.ModbusGateway.Command[x].ReadData controller tags depending

on the configured function type:

2 If the Modbus Gateway block uses a READ function type:

The data will be read to the AFC56.ModbusGateway.Command[x].ReadData[
]
array.

If the Modbus Gateway block uses a WRITE function type:

The data will be written from the AFC56.Modbus.Gateway[x].WriteData[ ]

array.

Note: The BID and BOD controller tags are automatically generated by the logic so you do not
have to write any value to these controller tags.

Advertising
This manual is related to the following products: