MVI56-AFC Backplane Communication

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 196 of 316

ProSoft Technology, Inc.

February 25, 2011

Special Notes
 If Bit 0 (F) of the Block ID element of the input Function Block is set:

o

Indicates Modbus exception: Illegal function (requested number of

registers is 0).

 If Bit 1 (A) of the Block ID element of the Input Function Block is set:

o

Indicates Modbus exception: Illegal address (an attempt to access one or

more non-existent Modbus registers).

 If Bit 2 (V) of the Block ID element of the Input Function Block is set:

o

Indicates Modbus exception: Illegal data value (never occurs for a "read"

function).

Note: If any of the above three bits are set, it indicates that no action on the OFB has been taken
by the AFC module.
Note: Refer to Function Block Structure (page 168) for information on Bit 8 and 9 settings.

11.2.12 Function Block Definition - 20, 21: Modbus Gateway Write

Output Function Block ID
Function Code 20: Write to Modbus Registers in the PRIMARY Slave HOLDING
register bank.

Function Code 21: Write to Modbus Registers in the VIRTUAL Slave HOLDING
register bank.