Modbus Database

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 72 of 316

ProSoft Technology, Inc.

February 25, 2011

5.2.3 Meter-relative Data

Meter-relative data starts at absolute holding register address 8000 and occupies

2000 words of data for each meter channel.

The meter-relative addresses are offsets within each meter data area. The

correct absolute address is calculated by the following formula (assumes meters

are numbered starting with 1):

(absolute address) = (2000 * (meter number-1)) + 8000 + (meter relative
address)

In the Modbus Dictionary dialog box, addresses listed for the selected meter are

absolute addresses, so you should subtract the appropriate multiple of 8000 to

calculate the meter-relative address.