2.3.6 Downloading the Project to the Module

1 Click P

ROJECT

/

D

OWNLOAD

P

ROJECT

.

2 This action opens the Local Port Settings window. Enter the port parameters

to use, and then click D

ONE

.

3 During the download operation, the following progress window is displayed:

4 When the file transfer is complete, the following window is displayed:

Note: The virtual slave remapping data (page 74) is not downloaded during the procedure because
it requires a separate download operation.
Troubleshooting Tip: If the AFC Manager displays an "Illegal Data Value" message, it typically
indicates an invalid meter type or product group configuration. The module does not accept a
configuration file that attempts to change a meter type or product group for a meter that is currently
enabled. Disable all meters, change the meter types and product groups, and then enable the
meters again.