MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 138 of 316

ProSoft Technology, Inc.

February 25, 2011

9.5.8 Other Considerations

Expired Events
If the starting event number is sufficiently small relative to the events on file (in

particular, if it is 1999 or more before the number of the next event to be

recorded), then that event is no longer on file and has already been overwritten.

In this case, the event returned by a Fetch is all zero. This is not an issue for the

Active host, especially when the event log is configured to be locked, as the

Active host is interested only in non-downloaded events and those always remain

on file with a locked log. But for Passive hosts, and when the event log is

configured as unlocked, download sessions must be performed frequently

enough so that the requested events still remain on file. Because event numbers

wrap from 65535 to 0, and because events that have not yet been written do not

in fact exist and have never existed, an event number that is numerically equal to

or greater than the number of the next event to be recorded is deemed to be the

number of an event from the previous wrap cycle.

Persistence
A log-download session does not survive a reset of the module (e.g. power

cycle).