ProSoft Technology MVI56-AFC User Manual

Page 296

Advertising
background image

Reference

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 296 of 316

ProSoft Technology, Inc.

February 25, 2011

14.7 Modbus Port configuration

Configuration of the serial ports is stored in these blocks of the Modbus table:

Address

Type

Description

Ph00102 to Ph00105

Bm

Port 1 configuration

Ph00106 to Ph00109

Bm

Port 2 configuration

Ph00110 to Ph00113

Bm

Port 3 configuration


Each group of registers specifies configuration of the corresponding serial port.

The four registers of each block are interpreted as follows:

Ofs

Type

Tag

Contents

+0

Bm

Uart

UART parameters and port options

+1.L

By

TmoC

LSB: Timeout for CTS

+1.H

By

TmoR

MSB: Master mode receive timeout

+2

By

Dly1

Delay before first data after CTS

+3

By

Dly0

Delay after last data before ~RTS


The CTS timeout and both delays are in units of 5ms (200Hz system clock), with

valid values from 0 thru 255, and are significant only for transmission of outgoing

Modbus messages. The receive timeout is in units of 0.1 second, with valid

values from 0 thru 255 (where 0 implies the default of 5, that is, one-half second),

and is significant only for the last port when configured as a Modbus master. The

UART parameters and port options word is a bitmap:

Bit

Parameter

Value

bits 0 to 2

Baud

000: none; see below
001: 300 baud
010: 600 baud
011: 1200 baud
100: 2400 baud
101: 4800 baud
110: 9600 baud
111: 19200 baud

bits 3 to 4

Parity

00: no parity
01: odd parity
10: even parity
11: no parity (should not be used)

bit 5

Data bits

0: 8 data bits
1: 7 data bits

bit 6

Stop bits

0: 1 stop bit
1: 2 stop bits

Advertising