12.3.4 Wallclock

After the module powers up, it will not perform flow calculation until it receives

valid wallclock information from the processor. The sample ladder logic uses the

processor internal clock as the source of the wallclock information.
Configure the processor time and date information:
1 Right-Click on Controller MVI56-AFC folder
2 Click on Properties
3 Select the Date/Time tab
4 Enter a valid date and time information.
After the AFC56.Flags.AFC_Set_Clock bit is toggled, the logic will move the date

and time information from the processor to the MVI56-AFC module.

The AFC56.Flags.AFC_Set_Clock bit is latched in the power up routine, in order

to guarantee that the module will be up and running after power up.

After the ladder logic receives the input block back from the module it unlatches

the AFC56.Flags.AFC_Set_Clock bit.
You may want to periodically synchronize the processor and the module’s

wallclock, especially when the date and time information is received from a

remote station. In this case, further ladder logic is required from you to

periodically toggle the AFC56.Flags.AFC_Set_Clock bit.