MVI56-AFC ♦ ControlLogix Platform

Introduction

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 15 of 316

February 25, 2011

1.3

Configuration Modification Lockout and Seal

The MVI56-AFC application configuration can be certified and sealed with a user-

installable Lockout jumper and a tamper-evident lead seal. The Lockout jumper

and seal are commonly required for Weights & Measures certification, or custody

transfer applications.

Important: When the jumper is installed, the module will not accept configuration changes to
Sealable Parameters, which are parameters that affect the accuracy of flow calculation. Before
breaking the seal to remove the jumper, you should verify the steps required to recertify the module
with the appropriate regulatory agency.


For more information on sealing procedures, refer to "Sealing Provisions", on

page 8 of the MVI56-AFC Custody Transfer Certification document, which is

available from the ProSoft Technology web site at http://www.prosoft-

technology.com/content/view/full/4613