MVI56-AFC ♦ ControlLogix Platform

MVI56-AFC Backplane Communication

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 187 of 316

February 25, 2011

Description
This block fetches a summary of the meter type and product group, which may

be used by the PLC to tailor its logic for providing process input values to the

AFC. Since there is no significant output, the "ignore output" bit (bit 8) has no

function. For firmware version 2.05 and later, non-zero stream information is

returned; for firmware version 2.04, the one stream is always enabled and active

which renders stream information redundant, and returned stream information is

all zero. The summary is returned as a single element of data, a bitmap having

this layout:

Bit

Description

0

meter is in alarm

1

meter is enabled

2

[spare]

3

[spare]

4

metering device is linear (pulse)

5

product phase is liquid

6

primary input is flow rate / frequency

7

[spare]

8

stream 1 enabled

9:

stream 2 enabled

10

stream 3 enabled

11

stream 4 enabled

12 to 13:

number of active stream (0-based: 0 thru 3)

14

[spare]

15

[spare]

11.2.8 Function Block Definition - 11: Meter Analysis, 32-bit

Note: Currently, this function is only available on the MVI56- AFC. For all other platforms continue
to use AFC Manager 2.05 or earlier.

Output Function Block ID

Advertising