8 monitoring, 1 device overload monitoring (ixt), Monitoring – Lenze 8400 BaseLine D User Manual

Page 104: Device overload monitoring (ixt), 5motor control (mctrl)

Advertising
background image

5

Motor control (MCTRL)

5.8

Monitoring

104

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.8

Monitoring

Many monitoring functions that are integrated into the controller can detect errors and thus protect

the device/motor from damage or overload.

• Detailed information on the individual monitoring functions can be found in the following sub-

chapters.

Parameterisable responses
If a monitoring function trips, the response set via the corresponding parameter is carried out. The

following responses can be selected:

• "No response": Response/monitoring is deactivated.
• "Fault": Change of the operating status by a pulse inhibit of the power output stage.
• "Warning": Operating status of the controller remains unchanged. Only a message is entered

into the logbook of the controller.

Related topics:

Device states

( 54)

Diagnostics & error management

( 142)

Basics on error handling in the controller

( 142)

Error messages of the operating system

( 153)

5.8.1

Device overload monitoring (Ixt)

In

C064/1...3

displays the device utilisation (ixt) in [%] in different time intervals:

• If the device utilisation reaches the switch-off threshold set in

C123

:

• The error response set in

C604

will be carried out (Lenze setting: "Warning").

• The "

OC5: Ixt overload

" error message will be entered into the logbook.

• A setting of

C604

= "0: No Reaction" deactivates the monitoring.

Monitoring

Response

(Lenze setting)

Parameter

Device overload monitoring (Ixt)

Warning

C604

Motor load monitoring (I2xt)

Warning

C606

Brake resistor monitoring (I2xt)

No Reaction

C574

Mains phase failure monitoring

Warning

C565

Parameter

Info

C064/1

Device utilisation (Ixt)

• Maximum value of the pulse utilisation (

C064/2

)

and permanent utilisation (

C064/3

).

C064/2

Device utilisation (Ixt) 15s

• Pulse utilisation over the last 15 seconds (only for loads >160 %).

C064/3

Device utilisation (Ixt) 3 min

• Permanent utilisation over the last 3 minutes.

Highlighted in grey = display parameter

Advertising