Parameter reference

9.2

Parameter list | C00137

190

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00137

C00141

Parameter | Name:

C00137 | Device state

Data type: UNSIGNED_16

Index: 24438

d

= 5F76

h

Display of the current device state
Selection list

(read only)

0 Reserved
1 Init
2 MotorIdent
3 ReadyToSwitchON
4 SwitchedON
5 OperationEnable
6 Reserved
7 Trouble
8 Fault
9 Reserved

10 SafeTorqueOff
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00141 | Device settings

Data type: UNSIGNED_8

Index: 24434

d

= 5F72

h

As of version 03.00.00

Selection list

0 Inactive
1 Active

Subcodes

Lenze setting

Info

C00141/1

0: Inactive

Always save parameters

• When this function is activated, every parameter

change is saved in the memory module. A manual sa-

ving of parameter sets is not required anymore.

Note:

Activating this function is not permissible if parameters

are changed very frequently (e.g. in case of cyclic writing

of parameters via a bus system).

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1