Drive application

7.1

Parameterisation dialog

124

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Tip!
When you click the Signal flow button, you will get one dialog level down to the signal flow

of the application.

L_MPot_1: Use

(

C806

)

0: No

Alternatively, the main speed setpoint can be generated

via a motor potentiometer function.

• In the Lenze setting, the motor potentiometer func-

tion is deactivated.

• Activation is possible via

C806

or via the

bMPotEnable input.

• The behaviour of the motor potentiometer during

switch-on of the drive system can be selected in

C805

.

• For a detailed functional description see

FB

L_MPot_1

.

( 226)

Accel. time - main setpoint

(

C012

)

2.0 s

The setpoint is led via a ramp function generator with li-

near characteristic. The ramp function generator con-

verts setpoint step-changes at the input into a ramp.

• For a detailed functional description see

FB

L_NSet_1

.

( 230)

Decel. time - main setpoint

(

C013

)

2.0 s

Reference speed

(

C011

)

1500 rpm

All speed setpoint selections are provided in % and al-

ways refer to the reference speed set in

C011

.

The motor reference speed is given on the motor name-

plate.

Deceleration time - quick

stop

(

C105

)

5.0 s

When "quick stop" is requested, the motor control is de-

coupled from the setpoint selection and within the de-

celeration time parameterised in

C105

, the motor is

brought to a standstill in (n

act

= 0).

Activate/Deactivate quick stop ( 51)

Fixed setpoint 1

(

C039/1

)

40.0 %

A fixed setpoint for the setpoint generator can be acti-

vated instead of the main setpoint via the selection in-

puts bJogSpeed1 and bJogSpeed2.

• The fixed setpoints are selected in [%] based on the

reference speed (

C011

).

• For a detailed functional description see

FB

L_NSet_1

.

( 230)

Fixed setpoint 2

(

C039/2

)

60.0 %

Fixed setpoint 3

(

C039/3

)

80.0 %

Parameter

Lenze setting

Info

Value Unit

Advertising