6i/o terminals – Lenze 8400 BaseLine D User Manual

Page 118

Advertising
background image

6

I/O terminals

6.3

User-defined terminal assignment

118

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Possibility 2: Change terminal assignment by means of the signal flow shown
Procedure:

1. Go to the Application parameters tab.
2. Go to the Application Parameters tab and click on the Signal flow button in order to change to

the dialog level OverviewSignal flow.

3. In the bJogSpeed2 list field, set the selection "0: Not interconnected".
4. In the bSetQuickstop list field, set the "12: DigIn_bIn2" selection.

6.3.3

Changing the terminal assignment via configuration parameters

The preconfigured terminal assignment can be reconfigured via a bus system, with the keypad or

with the »Engineer« by means of configuration parameters.

• Each configuration parameter represents a signal input of a function block, a system block or an

application block.

• Each configuration parameter contains a selection list with output signals of the same type of

data.

• Logical linking is thus carried out by selecting the output signal for the corresponding signal in-

put.

In the following example, digital output 1 (LS_DigitalOutput.bOut1 input) is logically linked to the

status signal "Drive ready" (LA_nCtrl_bDriveReady output signal):

Tip!
An overview of all configuration parameters and their Lenze setting in the different control

modes is provided in the chapter "

Pre-assignment of the drive application

".

( 134)