Motor control (MCTRL)

5.6

Parameterisable additional functions

98

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.6.3.1

Manual DC-injection braking (DCB)

DC-injection braking can be manually activated via the bSetDCBrake process input.

• For HIGH-active inputs, DC-injection braking is active as long as the signal is at HIGH level.
• After the hold time ((

C107

) has expired, the controller sets the pulse inhibit (CINH).

Tip!

• In the preset "Terminals 0" control mode, DC-injection braking can be manually activa-

ted via the digital input DI3.

• In the preset "Terminals 11" control mode, DC-injection braking can be manually activa-

ted via the digital input DI2.

5.6.3.2

Automatic DC-injection braking (Auto-DCB)

"Automatic DC-injection braking" (referred to in the following as "Auto-DCB") can be used if there is
a requirement that the drive be isolated from the supply at n

0.

Function
For understanding the auto-DCB function, it is necessary to distinguish between three different ty-

pes of operation:

A. The drive has been enabled and, in the course of operation, the speed setpoint falls below the

Auto-DCB threshold.

• In case of operation without speed feedback, a braking current (

C036

) is injected. After the

auto-DCB hold time (

C106

) has expired, the motor is deenergised via the auto-DCB function,

i.e. a controller inhibit (CINH) is set.

B. When the controller is enabled, the drive is at standstill (n = 0).

If the enabled drive is to start, the speed setpoint passed via the acceleration ramp must exceed

the auto-DCB threshold (

C019

). Below this threshold, the motor will not be energised.

C. When the controller is enabled, the motor (still) rotates at a speed which is above the auto DCB

threshold. If the speed setpoint reached via the acceleration ramp exceeds the auto DCB thres-

hold

C019

), the motor will be energised and the drive will be "caught".

Flying restart function

( 95)

How to set the automatic DC-injection braking

1. Set a hold time in

C106

> 0 s.

• Automatic DC-injection braking is active for the time set.
• In case of operation without speed feedback, the braking current set in

C036

is injected

• After the set hold time has expired, the controller sets a pulse inhibit.

2. Set the operating threshold in

C019

.

• The operating threshold can serve to set a dead band in the setpoint. If DC-injection bra-

king is not to be active then,

C106

must be set to a value of "0".