Page 160: Xx.0144.00004, Xx.0144.00031, 8diagnostics & error management

Advertising
background image

8

Diagnostics & error management

8.7

Error messages of the operating system

160

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

PS01: No memory module [xx.0144.00001]

PS02: Par. set invalid [xx.0144.00002]

PS03: Par. set device invalid [xx.0144.00003]

PS04: Par. set device incompatible [xx.0144.00004]

PS31: Ident. error [xx.0144.00031]

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

Memory module is either not available or not snapped

into place correctly.

• If a memory module has been provided: Plug the me-

mory module into the slot of the standard device in-

tended for this purpose.

• If a memory module has been provided: Check if the

memory module has been plugged-in correctly.

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

The parameter set saved to the memory module is inva-

lid because it has not been saved completely.

• This can be due to voltage failure or caused by remo-

ving the memory module while saving the parameter

set.

Ensure voltage supply during the storage process and

that the module remains plugged into the slot.

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

The parameter set in the device is invalid.

Consultation with Lenze required.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  Warning

Cause

Remedy

The parameter set saved to the memory module is in-

compatible to the standard device.

• An incompatibility of the parameter set is caused e.g.

when the memory module of an 8400 StateLine is

plugged into an 8400 BaseLine or the parameter set in

the memory module has a higher version than expec-

ted by the standard device.

When the memory modules are exchanged, observe the

downward compatibility:

• OK: BaseLine V2.0 to BaseLine V3.0

• Not OK: StateLine Vx.x to BaseLine Vx.x

• Not OK: BaseLine V3.0 to BaseLine < V3.0

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

Incompatible or unknown HW components have been

found.

• Check which HW components are faulty (

C203/x

: Pro-

duct type code).

• Check temperature range of the device at the start.

• Check whether a software update at Lenze is possible.

Advertising