C00007 | control mode, C00010 | minimum analog setpoint, C007 – Lenze 8400 BaseLine D User Manual

Page 174: Selection of contro, C010/1, C010, De in, 9parameter reference

Advertising
background image

9

Parameter reference

9.2

Parameter list | C00007

174

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00007

C00010

Parameter | Name:

C00007 | Control mode

Data type: UNSIGNED_16

Index: 24568

d

= 5FF8

h

Selection of how the application is to be controlled.
Selection list

(Lenze setting printed in bold)

Info

0 Wiring has changed

This display appears when the preset configuration has

been reparameterised via the connection parameters.

10 Terminals 0

The technology application is controlled via the digital

input terminals of the controller:

• DI1 = fixed setpoint 1/3

• DI2 = fixed setpoint 2/3

• DI3 = activate DC injection braking

• DI4 = change of direction of rotation

12 Terminals 2

The technology application is controlled via the digital

input terminals of the controller:

• DI1 = fixed setpoint 1/3

• DI2 = fixed setpoint 2/3

• DI3 = quick stop

• DI4 = change of direction of rotation

14 Terminals 11

The technology application is controlled via the digital

input terminals of the controller:

• DI1 = change of direction of rotation

• DI2 = activate DC injection braking

• DI3 = motor potentiometer: Higher speed

• DI4 = motor potentiometer: Lower speed

16 Terminals 16

The technology application is controlled via the digital

input terminals of the controller:

• DI1 = fixed setpoint 1/3

• DI2 = fixed setpoint 2/3

• DI3 = CW rotation/quick stop

• DI4 = CCW rotation/quick stop

20 Keypad

The technology application is controlled via the keypad:

C00002

: Device commands

C00003

: Status of last device command

C00727

: Executing control commands

C00728

: Selecting analog setpoints

 Increase speed

 Reduce speed

21 PC

The technology application is controlled via the "Free pa-

rameters" of the controller (PC control).

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00010 | Minimum analog setpoint

Data type: INTEGER_16

Index: 24565

d

= 5FF5

h

As of version 03.00.00

Lower limit for analog input

Analog terminals

Setting range

(min. value | unit | max. value)

0.0

%

100.0

Subcodes

Lenze setting

Info

C00010/1

0.0 %

Min. analog setpoint

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100