C00802 | l_mpot_1: acceleration time, C00803 | l_mpot_1: deceleration time, C00804 | l_mpot_1: inactive fct – Lenze 8400 BaseLine D User Manual

Page 214: C00805 | l_mpot_1: init fct, C805, C802, C803, C804, 9parameter reference

Advertising
background image

9

Parameter reference

9.2

Parameter list | C00802

214

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00802

C00803

C00804

C00805

Parameter | Name:

C00802 | L_MPot_1: Acceleration time

Data type: UNSIGNED_16

Index: 23773

d

= 5CDD

h

FB

L_MPot_1

: Acceleration time of the motor potentiometer function

Setting range

(min. value | unit | max. value)

Lenze setting

0.1

s

999.9 10.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00803 | L_MPot_1: Deceleration time

Data type: UNSIGNED_16

Index: 23772

d

= 5CDC

h

FB

L_MPot_1

: Deceleration time of the motor potentiometer function

Setting range

(min. value | unit | max. value)

Lenze setting

0.1

s

999.9 10.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00804 | L_MPot_1: Inactive fct.

Data type: UNSIGNED_8

Index: 23771

d

= 5CDB

h

FB

L_MPot_1

: Selection of the response when deactivating the motor potentiometer via the bInAct input

Selection list

(Lenze setting printed in bold)

Info

0 Keep value

Keep output value

1 Deceleration to 0

Deceleration via ramp to 0

2 Deceleration to lower limit

Deceleration via ramp to lower limit (

C00801

)

3 Without ramp to 0

Jump to 0

4 Without ramp to lower limit

Jump to lower limit (

C00800

)

5 Acceleration to upper limit

Acceleration via ramp to upper limit (

C00800

)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00805 | L_MPot_1: Init fct.

Data type: UNSIGNED_8

Index: 23770

d

= 5CDA

h

FB

L_MPot_1

: Selection of the response when switching on the device

Selection list

(Lenze setting printed in bold)

0 Load last value
1 Load lower limit
2 Load 0

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1