6i/o terminals – Lenze 8400 BaseLine D User Manual

Page 121

Advertising
background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

121

6

I/O terminals

6.4

Electrical data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

DI1 ... DI4

Digital inputs (according to IEC 61131-2, type 1)

LOW level: 0 ... +2.5 V

HIGH level: +10 ... +30 V

Input current: 4 mA per input (at 12 V supply of terminal 12I)

Electric strength of external voltage: ±30 V, permanent

Input impedance: 3.3 kΩ (2.0 kΩ ... 5.0 kΩ)

Processing cycle: 1 kHz (1 ms)

24E

External 24-V voltage supply

Input voltage: 24 V according to IEC 61131-2

DC 15.0 ... 30.0 V

Max. residual ripple ±5 %

SELV/PELV

Polarity reversal protection: In case of polarity reversal, the internal 12-V supply is active;

no destruction.

Current consumption: ≈ 50 mA during operation

DO1

Digital output (according to IEC 61131-2, type 1

LOW level: 0 ... +5 V

HIGH level: +15 ... +30 V

(independent of voltage at X4/24E)

Output current: max. 50 mA

(external resistance > 480 Ω at 24 V)

Electric strength of external voltage: +30 V

Integrated polarity reversal protection diode for switching

inductive loads

Processing cycle: 1 kHz (1 ms)

Behaviour in case of overload: Reduced voltage or periodical connection/disconnection

NO / COM

Relay output

• Potential-free contact (NO contact)

• AC 250 V / 3 A

• DC 24 V / 2 A ... 240 V / 0.22 A (with suppressor circuit)

Important: The minimum load must not fall below 12 V and 5 mA.

Terminal

Application / electrical data

Advertising