2 setting the error response, Setting the error response, 8diagnostics & error management – Lenze 8400 BaseLine D User Manual

Page 150

Advertising
background image

8

Diagnostics & error management

8.5

Monitoring

150

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.5.2

Setting the error response

When a monitoring function responds, the response set for this monitoring function (Trouble, Fault,

etc.) will be triggered.

• For many monitoring functions the response can be individually parameterised via parameters.

Tip!
The table in chapter "

Short overview (A-Z)

" contains the error messages for which the re-

sponse can be set .

( 156)

Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold has been exceeded.

• The corresponding preset threshold values can be changed via the following parameters:

Parameter

Info

Lenze setting

Value Unit

C120

Motor overload threshold (I²xt)

100 %

C123

Device utilisat. threshold (Ixt)

100 %

C909/1

Max. positive speed

120 %

C909/2

Max. negative speed

120 %

C910/1

Max. positive output frequency

300 Hz

C910/2

Max. negative output frequency

300 Hz