2 l_nset_1, L_nset_1 ( 230), L_nset_1 – Lenze 8400 BaseLine D User Manual

Page 230: L_nset, 10 function library

Advertising
background image

10

Function library

10.2

L_NSet_1

230

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.2

L_NSet_1

This FB is used for general signal processing of process values and is provided with the following

functions:

• Ramp function generator

• With linear ramps for main setpoint path
• With S-shaped ramp (PT1 rounding)

• Internal limitation of the input signal
• 3 fixed setpoints (JOG setpoints)

Inputs

Outputs

Identifier

Data type

Information/possible settings

bRfg0

BOOL

Leading the main setpoint integrator to 0 within the current Ti times

TRUE The current value of the main setpoint integrator is led to "0" within

the Ti time set.

bNSetInv

BOOL

Signal inversion for the main setpoint

TRUE Main setpoint signal is inverted.

nNset_a

INT

Main setpoint signal

• Scaling: 16384 ≡ 100 %

• Other signals are also permitted

bJog1 / bJog2

BOOL

Selection inputs for fixed changeover setpoints (JOG setpoints) for the main setpoint

• Selection inputs are binary coded.

Identifier

Data type

Value/meaning

nNOut_a

INT

Speed setpoint output signal

• Scaling: 16384 ≡ 100 %