5motor control (mctrl) – Lenze 8400 BaseLine D User Manual

Page 106

Advertising
background image

5

Motor control (MCTRL)

5.8

Monitoring

106

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

[5-5]

Tripping characteristic of the I

2

xt monitoring

Example:

C120

= I

r

/I

rated

x 100 %

C054

= 150 % rated motor current

• After approx. 60 seconds,

C066

has reached the final value100 % at output frequencies

f > 40 Hz.

• The controller outputs the "

OC6: I2xt overload motor" error message

and triggers the response

set in

C606

(default setting: "Warning").

Tip!

• If forced ventilated motors are used, a premature response of the overload threshold can

be avoided by deactivating this function if necessary (

C606

= "0: No Reaction").

• The current limits set in

C022

and

C023

influence the I

2

xt calculation only in an indirect

way. However, the operation of the motor at maximum possible load can be averted.

Defining current and speed limits

( 77)

f: Output frequency

t: Release time

I

rated

: Rated controller current at a switching frequency of f = 8 kHz

I

r

: Rated motor current (see nameplate of motor)

C054

: Apparent motor current

C120

: Motor overload threshold

60

180

240

300

360

t [s]

0.5

0

0

1.0

1.5

2.0

C00054

I

r

120

f = 0 Hz

f = 20 Hz

f > 40 Hz

I x 100 %

I

r

N

C00120 <

I x 100 %

I

r

N

C00120 =

I x 100 %

I

r

N

C00120 >