Commissioning

3.3

Commissioning with integrated keypad

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.3.4

Enable controller and select speed

When the controller is in the "

SwitchedON

" state:

1. Enable controller:

Set terminal X4/RFR to HIGH level or close contact to terminal X4/12I n.

2. Select speed:

• In the "Terminals 0" by selecting a voltage at the analog input or by selecting a fixed setpoint

via the digital inputs DI1/DI2.

Tip!
More control functions in the "Terminals 0" control mode:

• DI3: HIGH level ≡ request DC-injection braking
• DI4: HIGH level ≡ request change of direction of rotation

Note!

If the controller is enabled at power-on and the auto-start option is activated in

C142

"In-

hibit at power-on" (Lenze setting), the controller remains in the "

ReadyToSwitchON

" sta-

te.
For changing to the "

SwitchedON

" state, first deactivate the controller enable: Set termi-

nal X4/RFR to LOW level or open contact to terminal X4/12I.

DI1

DI2

Speed selection

LOW

LOW

The setpoint speed is selected via the analog input 1

• Scaling: 10 V ≡ 100 % ≡ reference speed (

C011

)

HIGH

LOW

The fixed setpoint 1 (

C039/1

) is used as setpoint speed.

• Lenze setting: 40 % of the reference speed (

C011

)

LOW

HIGH

The fixed setpoint 2 (

C039/2

) is used as setpoint speed.

• Lenze setting: 60 % of the reference speed (

C011

)

HIGH

HIGH

The fixed setpoint 3 (

C039/3

) is used as setpoint speed.

• Lenze setting: 80 % of the reference speed (

C011

)

Note!

Observe the actual speed value (display in

C051

) as well as the

LED status display

and

Display messages

indicated in the integrated keypad.