Oc6: i2xt motor overload, Error m, Oc6: i2xt overload motor" error message – Lenze 8400 BaseLine D User Manual

Page 159: Oc12: i2xt brake resistor overload, Xx.0125.00001, Xx.0123.00057, Xx.0123.00017, Xx.0123.00105, Xx.0123.00065, 8diagnostics & error management

Advertising
background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

159

8

Diagnostics & error management

8.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

OC2: Power section - earth fault [xx.0123.00017]

ID1: Motor data identification error [xx.0123.00057]

OC12: I2xt overload - brake resistor [xx.0123.00065]

OC6: I2xt overload - motor [xx.0123.00105]

An01: AIN1_I < 4 mA [xx.0125.00001]

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

The device has recognised an earth fault at one of the

motor phases. To protect the device electronics, the in-

verter control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If motor filter, motor cable length, and cable type

(shielding capacity) are dimensioned incorrectly, this

error message may occur due to leakage currents to

PE.

• Check motor connections and the corresponding plug

connector on the device.

• Use motor filters, cable lengths, and cable types re-

commended by Lenze.

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

The device has detected an error during the motor data

identification.

Possible causes:

• Interrupted motor cable.

• Switched-off power section during the identification.

• Implausible start parameter settings.

• Check the motor connections and the corresponding

plug connector on the device and, if necessary, the

motor terminal box.

• Correct start parameters for the motor parameter

identification (motor nameplate data).

• Stable power supply of the device.

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

Too frequent and too long braking processes.

Check drive dimensioning.

Response (Lenze setting printed in bold)

Setting:

C606

( Adjustable response)

None  Fault  Trouble  WarningLocked

Cause

Remedy

Thermal overload of the motor.

• Observe load requirements.

• Correct dimensioning if necessary.

• In case of VFCplus operation: Check Vmin boost

(

C016

).

Set Vmin boost

Response (Lenze setting printed in bold)

Setting:

C598/1

( Adjustable response)

None  Fault  Trouble  WarningLocked

Cause

Remedy

Open-circuit monitoring for analog input has tripped.

• Only if the analog input has been configured as a cur-

rent loop of 4 ... 20 (

C034/1

= 2).

• Check wiring of the analog X4/A1U input terminal for

open circuit.

• Check connection of the external 250-Ω load resistor

between the terminals A1U and GND.

• Check minimum current values of the signal sources.

Advertising