2 motorident, 3 safetorqueoff, Motorident – Lenze 8400 BaseLine D User Manual

Page 57: Safetorqueoff, Device state, 4device control (dctrl), Stop

Advertising
background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

57

4

Device control (DCTRL)

4.2

Device states

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.2

MotorIdent

In the "MotorIdent" device state

• is the controller when being in the "

SwitchedON

" state and having activated the "

Identify motor

parameters

" device command and being enabled.

• the application remains active.
• all system interfaces (IO, bus systems, etc.) remain active.
• error monitoring remains active
• the inverter is controlled independently of the setpoint sources.

After the motor parameter identification is completed, the state changes back to "

SwitchedON

".

Tip!
Detailed information on motor parameter identification can be found in the "

Automatic

motor data identification

" subchapter on motor control.

( 71)

4.2.3

SafeTorqueOff

In the "SafeTorqueOff" device state

• the controller can only be if a safety module is connected and the power section is supplied and

at least one of the two safe inputs SI1/SI2 is set to LOW level.

• the next transaction to the "

ReadyToSwitchON

" state takes place.

LED DRIVE READY

LED DRIVE ERROR

Display in

C137

Display in status word 1 (

C150

)

Bit 11

Bit 10

Bit 9

Bit 8

OFF

MotorIdent

0

0

1

0

Stop!

During motor parameter identification, the controller does not respond to setpoint

changes or control processes, (e.g. speed setpoints, quick stop, torque limitations).

LED DRIVE READY

LED DRIVE ERROR

Display in

C137

Display in status word 1 (

C150

)

Bit 11

Bit 10

Bit 9

Bit 8

OFF

SafeTorqueOff

1

0

1

0

Detailed and important information on the integrated safety system can be found in the

hardware manual!