5 user menu, User menu, User menu ( 23) – Lenze 8400 BaseLine D User Manual

Page 23: 2introduction: parameterising the controller

Advertising
background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

23

2

Introduction: Parameterising the controller

2.3

Internal Keypad

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

2.3.5

User menu

The user menu (menu -0-) contains a selection of frequently used parameters to be able to access

and change these parameters quickly.

• The integrated keypad serves to change the preset parameter selection in

C517

: Enter the codes

the user menu is to contain into the subcodes c001 ...c020. When "0" is set, no entry is displayed

in the user menu.

• The »Engineer« serves to configure the user menu on the User menu tab of the controller. Here,

additional functions are available for loading and saving the parameter selection.

The user menu contains the following parameters:

Code

Subcode

Info

Lenze setting

Value Unit

C051

-

Display of actual speed value

- rpm

C053

-

Display of DC-bus voltage

- V

C054

-

Display of motor current

- A

C061

-

Display of heatsink temperature

- °C

C137

-

Display of device status

-

C011

-

Reference speed

1500 rpm

C039

c001

Fixed setpoint 1

40.0 %

c002

Fixed setpoint 2

60.0 %

c003

Fixed setpoint 3

80.0 %

C012

-

Acceleration time - main setpoint

2.0 s

C013

-

Deceleration time - main setpoint

2.0 s

C015

-

V/f base frequency

50.0 Hz

C016

-

Vmin boost

0.0 %

C022

-

Imax in motor mode

47.00 A

C120

-

Motor overload threshold (I

2

xt)

100 %

C087

-

Rated motor speed

1460 rpm

C099

-

Display of firmware version

-

Highlighted in grey = display parameter

Note!

If the password protection is activated and no password or a wrong password is entered,

only these parameters can be accessed with the integrated keypad.

Password protection

( 24)