Parameter list | C00574

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00574

C00581

C00598

Parameter | Name:

C00574 | Resp. to brake resist. overtemp.

Data type: UNSIGNED_8

Index: 24001

d

= 5DC1

h

Response when the permanently set threshold for monitoring the brake resistor utilisation has been reached.
Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
4 WarningLocked

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00581 | Resp. to LS_SetError_x

Data type: UNSIGNED_8

Index: 23994

d

= 5DBA

h

Selection of the error responses for application error messages

• An application error message is tripped by a FALSE-TRUE edge at the binary inputs bSetError1...2.

Selection list

0 No Reaction
1 Fault
2 Trouble
4 WarningLocked

Subcodes

Lenze setting

Info

C00581/1

1: Fault

LS_SetError_1

: Resp. bSetError1

C00581/2

1: Fault

LS_SetError_1

: Resp. bSetError2

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00598 | Resp. to open circuit AINx

Data type: UNSIGNED_8

Index: 23977

d

= 5DA9

h

Configuration of monitoring the analog input

Analog terminals

Selection list

0 No Reaction
1 Fault
2 Trouble
4 WarningLocked

Subcodes

Lenze setting

Info

C00598/1

1: Fault

Response to open circuit at AIN1 when being configured

as 4 ... 20 mA-current loop

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1