V/f characteristic control (VFCplus)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.4

V/f characteristic control (VFCplus)

In case of the V/f characteristic control (VFCplus), the motor voltage of the inverter is determined by

means of a linear or quadratic characteristic depending on the field frequency or motor speed to be

generated. The voltage follows a preselected characteristic.

5.4.1

Parameterisation dialog/signal flow

Proceed as follows to open the dialog for parameterising the motor control:

1. »Engineer« Go to the Project view and select the 8400 BaseLine D controller.
2. Go to Workspace and change to the Application parameters tab.
3. Select the motor control from the Overview dialog level in the Motor control list field:

• "6: VFCplus: V/f linear" for linear characteristic or
• "8: VFCplus: V/f quadr" for square-law characteristic

4. Click the Motor control V/f button to change to the OverviewMotor control V/f dialog

box.

Stop!

• The following must be observed when operating drives with quadratic V/f characteri-

stic:

• Please always check whether the corresponding drive is suitable for operation with

a quadratic V/f characteristic!

• If your pump drive or fan drive is not suitable for operation with a quadratic V/f

characteristic, you must use either use the V/f characteristic control function with

a linear V/f characteristic or the sensorless vector control (SLVC).

• For adjustment, observe the thermal performance of the connected asynchronous

motor at low output frequencies.

• Usually, standard asynchronous motors with insulation class B can be operated for

a short time with their rated current in the frequency range 0 Hz ≤ f ≤ 25 Hz.

• Contact the motor manufacturer to get the exact setting values for the max. per-

missible motor current of self-ventilated motors in the lower speed range.

• If you select the quadratic V/f characteristic, we recommend to set a lower V

min

.

• The nameplate data of the motor (at least rated speed and rated frequency) must be

entered if, instead of a standard motor, an asynchronous motor is used with the fol-

lowing values:

• rated frequency ≠ 50 Hz (star) or
• rated frequency ≠ 87 Hz (delta) or
• number of pole pairs ≠ 2

Note!

When the auto DCB threshold is set (

C019

) > 0 rpm, there is no torque at the motor shaft

in the lower speed range!

Automatic DC-injection braking (Auto-DCB)

( 98)