C00033 | ainx: output value, C00034 | ainx: configuration, C00036 | dcb: current – Lenze 8400 BaseLine D User Manual

Page 179: C036, C034/1, C033/1, When, C00034/1, 9parameter reference

Advertising
background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

179

9

Parameter reference

9.2

Parameter list | C00033

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00033

C00034

C00036

Parameter | Name:

C00033 | AINx: Output value

Data type: INTEGER_16

Index: 24542

d

= 5FDE

h

Display of the output value in percent of the analog input amplifier

• 100 % ≡ 16384 ≡ +10 V / +20 mA

Analog terminals

Display range

(min. value | unit | max. value)

-199.9

%

199.9

Subcodes

Info

C00033/1

AIN1: Output value

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00034 | AINx: Configuration

Data type: UNSIGNED_8

Index: 24541

d

= 5FDD

h

Configuration of the analog input for current or voltage measurement

Analog terminals

Selection list

Info

0 0...+10 V

Input signal is voltage signal 0 V ... +10 V

• 0 V ... +10 V ≡ 0 % ... +100 %

1 0...+5V

With external load resistor (250 Ohms):

Input signal is the current signal 0 mA ... 20 mA

• 0 mA ... 20 mA ≡ 0 % ... +100 %

2 1...+5V (4...20mA)

With external load resistor (250 Ohms):

Input signal is the current signal 4 mA ... 20 mA

• 4 mA ... 20 mA ≡ 0 % ... +100 %

• The current loop is monitored for open circuit

(I < 4 mA) by the device.

Subcodes

Lenze setting

Info

C00034/1

0: 0...+10 V

AIN1: Config.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00036 | DCB: Current

Data type: INTEGER_16

Index: 24539

d

= 5FDB

h

Current value in [%] for DC-injection braking

• 100 % ≡ Imax in motor mode (

C00022

)

DC injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

150.0 50.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Advertising