5 remedies for undesired drive behaviour, Remedies for undesired drive behaviour, 5motor control (mctrl) – Lenze 8400 BaseLine D User Manual

Page 92

Advertising
background image

5

Motor control (MCTRL)

5.5

Sensorless vector control (SLVC)

92

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.5.5

Remedies for undesired drive behaviour

Drive behaviour

Remedy

Deviation between no-load current and magnetising

current or bad speed or torque accuracy.

Adapt the motor magnetising inductance (

C092

) for no-

load operation.

• If the no-load current is greater than the magnetising

current (

C095

) at 0.5-fold rated motor speed, the ma-

gnetising inductance must be reduced until the no-

load current and the magnetising current have the

same values.

• Otherwise, the magnetising inductance must be in-

creased.

Tendency of the correction of

C092:

PN: Rated motor power

Insufficient speed constancy at high load: Setpoint and

motor speed are not proportional anymore.

Caution: Overcompensation of the settings mentioned

under " Remedy" may result in unstable behaviour!

Via the slip compensation (

C021

, the speed stability un-

der high loads can be affected:

• If n

act

> n

slip

, reduce the value in

C021

• If n

act

< n

slip

, increase the value in

C021

Unstable control with higher speeds.

• Check the setting of the magnetising inductance

(

C092

) by comparing the current consumption in no-

load operation with the rated magnetising current

(

C095

)

• Optimise oscillation damping (

C234

).

"Short circuit" (OC1) error messages at short acceleration

time (

C012

) in proportion to the load (controller cannot

follow the dynamic processes).

Increase acceleration time (

C012

)/deceleration time

(

C013

).

Mechanical resonance at certain speeds.

The

L_NSet_1

function block masks out those speed ran-

ges that include resonance.

Speed variations in no-load operation for speeds > 1/3

rated speed.

Minimise speed oscillations with oscillation damping

(

C234

).

Drive runs unstable.

Check set motor data (nameplate data and equivalent

circuit diagram data).

Motor selection/Motor data ( 66)

Setpoint speed and actual speed differ strongly.

0,37

22

90

C0092

-15 %

+15 %

0

P [kW]

N

Advertising