Parameter list | C00120

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00120

C00122

C00123

C00134

Parameter | Name:

C00120 | Motor overload threshold (I²xt)

Data type: INTEGER_16

Index: 24455

d

= 5F87

h

Operating threshold for the error message "OC6: Motor overload (I²xt)"

• The response for reaching the threshold can be selected in

C00606

.

• The current thermal motor load is displayed in

C00066

.

Motor overload monitoring (I2xt)

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

250 100 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00122 | Initial value motor overload (I²xt)

Data type: UNSIGNED_16

Index: 24453

d

= 5F85

h

From version 03.04.00

The thermal motor load displayed in

C00066

is pre-initialised with the value set here when the device is connected

to the mains.

• If "100.00 %" is set, the last value at switching off the device is used for the initialisation.

• Recommended setting for operation according to UL: 50.00 %

Motor overload monitoring (I2xt)

Setting range

(min. value | unit | max. value)

0.00

%

100.00

Subcodes

Lenze setting

Info

C00122/1

0.00 %

Initial value motor overload (I²xt)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00123 | Device utilisation threshold (Ixt)

Data type: INTEGER_16

Index: 24452

d

= 5F84

h

Operating threshold for the error message "OC5: Device overload (Ixt)"

• The response for reaching the threshold can be selected in

C00604

.

• The current device utilisation is displayed in

C00064

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

100 100 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00134 | Ramp smoothing, main setpoint

Data type: UNSIGNED_8

Index: 24441

d

= 5F79

h

FB

L_NSet_1

: Configuration of the ramp smoothing for the main setpoint

Selection list

(Lenze setting printed in bold)

Info

0 Off

Ramp rounding deactivated

1 PT1 behaviour

Ramp rounding with PT1 behaviour

• The corresponding S-ramp time must be set in

C00182

.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1