Device control (DCTRL)

4.2

Device states

60

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.6

OperationEnabled

In the "OperationEnabled" state

• is the controller if the controller inhibit is deactivated and no trouble ("Trouble") and fault

("Fault") are existent.

• the operation is enabled and the motor follows the setpoint defined by the active application

(in case of sensorless vector control only after the magnetisation process is completed).

Depending on certain conditions, a state change takes place based on the "OperationEnabled" de-

vice state.

LED DRIVE READY

LED DRIVE ERROR

Display in

C137

Display in status word 1 (

C150

)

Bit 11

Bit 10

Bit 9

Bit 8

OFF

OperationEnabled

0

1

0

1

Change condition

Changeover to the device state

Terminal RFR = LOW level (controller inhibit).

SwitchedON

Undervoltage in the DC bus.

Trouble

/

Fault

(dependent on

C600/1

)

Error with error response "Trouble" occurs.

Trouble