3 setpoint inversion, 4 ramp function generator for the main setpoint, 5 s-shaped ramp – Lenze 8400 BaseLine D User Manual

Page 232: Setpoint inversion, Ramp function generator for the main setpoint, S-shaped ramp, 10 function library

Advertising
background image

10

Function library

10.2

L_NSet_1

232

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.2.3

Setpoint inversion

The output signal of the JOG function is led via an inverter.
The sign of the setpoint changes if bNSetInv is set to TRUE.

10.2.4

Ramp function generator for the main setpoint

The setpoint is now led via a ramp function generator with linear characteristic. The ramp function

generator converts setpoint step-changes at the input into a ramp.

[10-3] Acceleration and deceleration times

• t

ir

and t

if

are the desired times for changing between w1 and w2.

• The ramps for acceleration and deceleration can be set individually.

C012

: Acceleration time T

ir

C013

: Deceleration time T

if

• The t

ir

/t

if

values are converted into the required Ti times according to the following formula:

• When the bRfg0 output is set to TRUE, the ramp function generator brakes to 0 along its dece-

leration ramp.

10.2.5

S-shaped ramp

A PT1 element is connected downstream of the linear ramp function generator. This arrangement

implements an S-shaped ramp for a nearly jerk-free acceleration and deceleration.

• The PT1 element can be switched on/off via

C134

.

• The corresponding S-ramp time can be set under

C182

.

w1, w2 = change of the main setpoint as a function of t

ir

and t

if

RFG-OUT = output of the ramp function generator

RFG-OUT

100 %

w2

w1

t

0 %

t

ir

t

ir

T

ir

T

ir

T

ir

t

ir

100 %

w2 w1

-----------------------

=

T

if

t

if

100 %

w2 w1

-----------------------

=

Advertising