2 deactivate motor potentiometer, Deactivate motor potentiometer, 10 function library – Lenze 8400 BaseLine D User Manual
Page 229
Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05
229
10
Function library
10.1
L_MPot_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.1.2
Deactivate motor potentiometer
When the motor potentiometer is deactivated by setting bInAct to TRUE, the nOut_a output signal
responds according to the function selected in
[10-2] Example: Deactivation of the motor potentiometer if
= "1: Deceleration to 0"
When the motor potentiometer is deactivated, nOut_a is reduced to 0 % with the deceleration time wTif.
If it is activated again, nOut_a is increased again to nLowLimit with the acceleration time wTir.
nOut_a
t
t
TRUE
FALSE
bUp
t
TRUE
FALSE
bDown
nHighLimit
nLowLimit
0
wTir
wTif
wTir
t
TRUE
FALSE
bInAct
wTif
wTif
0
1