Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

229

10

Function library

10.1

L_MPot_1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.1.2

Deactivate motor potentiometer

When the motor potentiometer is deactivated by setting bInAct to TRUE, the nOut_a output signal

responds according to the function selected in

C804

.

[10-2] Example: Deactivation of the motor potentiometer if

C804

= "1: Deceleration to 0"

 When the motor potentiometer is deactivated, nOut_a is reduced to 0 % with the deceleration time wTif.

 If it is activated again, nOut_a is increased again to nLowLimit with the acceleration time wTir.

nOut_a

t

t

TRUE

FALSE

bUp

t

TRUE

FALSE

bDown

nHighLimit

nLowLimit

0

wTir

wTif

wTir

t

TRUE

FALSE

bInAct

wTif

wTif

0

1