C00016 | vfc: vmin boost, C00018 | switching frequency, C00019 | auto dcb: threshold – Lenze 8400 BaseLine D User Manual

Page 176: C016, C019, C018, With, Influe, Ction in, To-dcb threshold

Advertising
background image

9

Parameter reference

9.2

Parameter list | C00016

176

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00016

C00018

C00019

Parameter | Name:

C00016 | VFC: Vmin boost

Data type: UNSIGNED_16

Index: 24559

d

= 5FEF

h

Boost of the V/f voltage characteristic within the range of low speed or frequency values for the (

VFCplus

) V/f cha-

racteristic control.

• This may increase the starting torque.

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered auto-

matically. An automatic detection via the motor parameter identification is possible as well.

Motor control (MCTRL)

:

Setting Vmin boost

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

100.0 0.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00018 | Switching frequency

Data type: UNSIGNED_8

Index: 24557

d

= 5FED

h

Selection of the pulse width modulated switching frequency transferred from the inverter to the motor

• When a variable switching frequency is selected, the switching frequency may change as a function of the load

and rotational frequency.

Selection of the switching frequency

Selection list

(Lenze setting printed in bold)

1 4 kHz var./drive-optimised
2 8 kHz var./drive-optimised
3 16 kHz var./drive-optimised
5 2 kHz constant/drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised

21 8 kHz var/4 kHz min.
22 16 kHz var/4 kHz min.
23 16 kHz var/8 kHz min

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00019 | Auto DCB: Threshold

Data type: UNSIGNED_16

Index: 24556

d

= 5FEC

h

Setpoint speed threshold for automatic DC injection braking

• For speed setpoints with values below the thresholds a DC current is injected or the motor is not supplied with

current, depending on the setting.

DC injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0

rpm

9999 3 rpm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1