background image

5

Motor control (MCTRL)

5.8

Monitoring

108

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.8.4

Mains phase failure monitoring

The drive controller has a simple mains-phase failure detection function with which a mains phase

failure can be detected under load.

• In the case of power-adapted machines, approx. 50 % of the rated motor power must be excee-

ded so that a main-phase failure can be detected.

• If the mains phase failure monitoring is tripped:

• The error response set in

C565

will be carried out (Lenze setting: "Warning").

• The "

Su02: Mains voltage switched-off

" error message is entered into the logbook.

Stop!

Under load, the mains input of a three-phase controller can be destroyed if the device is

only supplied by two phases (e.g. if a mains phase fails).