5.4.3.1

Adapting the V/f base frequency

The V/f base frequency (

C015

) determines the slope of the V/f characteristic and has considerable

influence on the current, torque, and power performance of the motor.

• The setting in

C015

applies to all permitted mains voltages.

• Mains fluctuations or fluctuations of the DC-bus voltage (operation in generator mode) do not

need to be considered when the V/f base frequency is set. They are automatically compensated

for by the internal mains voltage compensation of the device.

• Depending on the setting in

C015

, it may be required to adapt the reference speed (

C011

) to tra-

verse the entire speed range of the motor.

• In standard applications, the V/f base frequency (

C015

) is set to the value of the rated motor fre-

quency (

C089

) as a typical value and corresponds to the data of the motor nameplate.

• Reference voltage for the V/f base frequency is the rated motor voltage (

C090

) according to mo-

tor nameplate.

Note!

87-Hz operation
4-pole asynchronous motors which are designed for a rated frequency of f = 50 Hz in star

connection can be operated in delta connection when being constantly excited up to f =

87 Hz.

• Advantages:

• Higher speed-setting range
• 73% higher power output in case of standard motors

• Motor current and motor power increase by the factor

.

• The field weakening range starts above 87 Hz.
• Generally, this process can also be used with motors which have different numbers of

pole pairs. In case of 2-pole asynchronous motors, the mechanical limit speed must be

maintained.