1 load lenze setting, 2 loading parameter settings, Load lenze setting – Lenze 8400 BaseLine D User Manual

Page 49: Loading parameter settings, 4device control (dctrl)

Advertising
background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

49

4

Device control (DCTRL)

4.1

Device commands

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.1.1

Load Lenze setting

The

C002/1

= "1: On / start" device command resets the parameters to the Lenze setting which are

saved in the controller firmware.

• Can only be executed if the controller is inhibited; otherwise, the feedback

C002/1

= "6: No ac-

cess - controller inhibit" will be returned".

• All parameter changes which have been carried out after the last time the parameter settings

were saved will be lost!

• This device command has an effect on the settings of the parameters of the operating system,

application and module.

How to load the Lenze setting:

1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/Inhibit cont-

roller" device command" (

C002/16

= "0: Off / ready").

2. Execute the "Load Lenze setting" device command

C002/1

= "1: On / start"

The load process may take a couple of seconds. After the device command has been called

in

C002/1

a dynamic status information ("Work in progress" W "Off / ready") is returned.

4.1.2

Loading parameter settings

The

C002/2

= "1: On / start" device command reloads all parameters from the memory module to

the controller.

• Can only be executed if the controller is inhibited; otherwise, the feedback

C002/2

= "6: No ac-

cess - controller inhibit" will be returned.

• All parameter changes which have been carried out after the last time the parameter settings

were saved will be lost!

• This device command has an effect on the settings of the parameters of the operating system,

application and module.

How to reload the starting parameter settings from the memory module:

1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/Inhibit cont-

roller" device command (

C002/16

= "0: Off / ready").

2. Execute the "Load Lenze setting" device command:

C002/2

= "1: On / start"

The load process may take a couple of seconds. After the device command has been called

in

C002/2

a dynamic status information ("Work in progress" W "Off / ready") is returned.

Note!

When the device is switched on, all parameters are automatically loaded from the me-

mory module to the main memory of the controller.