I/O terminals

6.2

Analog terminals

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2.1

Parameterising analog input

By clicking

on the Terminal assignment tab, you reach the parameterising dialog for the analog

input:

Short overview of parameters for the analog input:

Using the analog input as current input
In the Lenze setting, a voltage signal in the range 0 ... +10 V is evaluated via the analog input termi-

nal A1U.
For evaluating a current signal:

1. Connect external 250-Ω load resistor.
2. Make the following setting in

C034/1

:

• Selection "1: 0 ... +5 V" for 0 ... 20 mA current loop.
• Selection "2: +1 ... +5 V" for 4 ... 20 mA current loop

("life zero", with open-circuit monitoring).

3. With a configuration as 4 ... 20 mA current loop in

C598/1

, set the desired error response in the

event of open circuit (Lenze setting: "Fault").

Parameter

Info

Lenze setting

Value Unit

C034/1

AIN1: Config.

0: 0 ... +10 V

C026/1

AIN1: Offset

0.0 %

C027/1

AIN1: Gain

100.0 %

C010/1

AIN1: Minimum analog setpoint

0.0 %

C028/1

AIN1: Input voltage

- V

C033/1

AIN1: Output value (to application)

- %

C598/1

Resp. to open circuit AIN1

1: Fault

Highlighted in grey = display parameter