2 analog terminals, Analog terminals, 6i/o terminals – Lenze 8400 BaseLine D User Manual

Page 112

Advertising
background image

6

I/O terminals

6.2

Analog terminals

112

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2

Analog terminals

The controller is provided with an analog input for detecting a voltage signal. The voltage signal can

be e.g. an analog speed setpoint selection or the signal of an external sensor (temperature, pressure,

etc.).

• Possible voltage ranges:

• 0 ... +10 V (Lenze setting)
• 0 ... +5 V
• 1 ... +5 V

• An external 250-Ω load resistor and a respective parameter setting allow to implement a cur-

rent loop:

• 0 ... 20 mA, without open-circuit monitoring
• 4 ... 20 mA, with open-circuit monitoring

Parameterisation dialog in the »Engineer«:

Note!

To avoid undefined states, free input terminals of the controller must be assigned as

well, e.g. by applying 0 V to the terminal.

Button

Function

Parameterising analog input ( 113)

Open the parameterising dialog for assigning application inputs to the analog input.

Changing the terminal assignment with the »Engineer« ( 117)