Sage), Lu: dc bus undervoltage, Xx.0123.00015 – Lenze 8400 BaseLine D User Manual

Page 158: Xx.0123.00016, Xx.0119.00052, Xx.0123.00014, 8diagnostics & error management

Advertising
background image

8

Diagnostics & error management

8.7

Error messages of the operating system

158

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

OC9: Ixt overload - shutdown limit [xx.0119.00052]

OU: DC bus overvoltage [xx.0123.00014]

LU: DC bus undervoltage [xx.0123.00015]

OC1: Power section - short circuit [xx.0123.00016]

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

The Ixt overload check has tripped.

• Operating threshold = 110 % Ixt (fixed)

Possible causes:

• Wrong dimensioning of the device with regard to its

motor load.

• Load cycles are not complied with.

• Check and, if required, correct dimensioning of the

device and the motor load with regard to technical

data.

• Reduce motor load cycles (observe load cycles accor-

ding to documentation).

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

The device has detected an overvoltage in the DC bus. To

protect the device hardware, the inverter control is swit-

ched off.

• Depending on the configuration of the auto-start lock

function,

C142

serves to set that, if this error has been

tripped, the controller only starts after the controller

inhibit is switched.

• If this error message remains active longer than the

time set in

C601

a "Fault" is tripped.

• Reduce load in generator mode.

• Use a brake resistor.

• Use a regenerative power supply unit.

• Establish a DC-bus connection.

Response (Lenze setting printed in bold)

Setting:

C600/1

( Adjustable response)

None  Fault  Trouble  WarningLocked

Cause

Remedy

The device has detected a DC bus undervoltage. The in-

verter control is switched off because the drive proper-

ties of the motor control cannot be provided anymore

due to the DC bus undervoltage.

• Depending on the configuration of the auto-start lock

function,

C142

serves to set that, if this error has been

tripped, the controller only starts after the controller

inhibit is switched.

• Switch on mains supply or ensure sufficient supply via

DC bus.

• Adjust setting in

C142

if required.

Response (Lenze setting printed in bold)

None  Fault  Trouble  WarningLocked

Cause

Remedy

The device has recognised a short circuit of the motor

phases. To protect the device electronics, the inverter

control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If the device is inappropriately dimensioned with re-

gard to the motor load and the current limitation in

the controller (Imax controller) is set incorrectly, this

error message may also occur.

Motor control: Defining current limits

• Check motor connections and the corresponding plug

connector on the device.

• Only use permissible combinations of device power

and motor power.

• Do not set the dynamics of the current limitation con-

troller too high.