C00727 | ls_keypad: digital values, C00728 | ls_keypad: keypad analog values, C00800 | l_mpot_1: upper limit – Lenze 8400 BaseLine D User Manual

Page 213: C00801 | l_mpot_1: lower limit, C728/1, C728/2, Meterised via, Value set in, C800, With

Advertising
background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

213

9

Parameter reference

9.2

Parameter list | C00727

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00727

C00728

C00729

C00800

C00801

Parameter | Name:

C00727 | LS_Keypad: Digital values

Data type: UNSIGNED_8

Index: 23848

d

= 5D28

h

Executing control commands when operating via keypad
Setting range

(min. value | unit | max. value)

0

1

Subcodes

Lenze setting

Info

C00727/1

0

"1" ≡ request quick stop

C00727/2

0

"1" ≡ request DC-injection braking

C00727/3

0

"1" ≡ request change of direction of rotation

C00727/4

0

"1" ≡ request fixed speed setpoint 1

C00727/5

0

"1" ≡ request fixed speed setpoint 2

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00728 | LS_Keypad: Keypad analog values

Data type: INTEGER_16

Index: 23847

d

= 5D27

h

Selection of different setpoints when operating via keypad
Setting range

(min. value | unit | max. value)

-199.9

%

199.9

Subcodes

Lenze setting

Info

C00728/1

100.0 %

Torque limit in motor mode

C00728/2

100.0 %

Torque limit in generator mode

C00728/3

0.0 %

Setpoint speed

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00729 | Keypad/PC: Speed setpoint

Data type: INTEGER_16

Index: 23846

d

= 5D26

h

This code is for device-internal use only and must not be written to by the user!

Parameter | Name:

C00800 | L_MPot_1: Upper limit

Data type: INTEGER_16

Index: 23775

d

= 5CDF

h

FB

L_MPot_1

: Upper limit of the motor potentiometer function

Setting range

(min. value | unit | max. value)

Lenze setting

-199.9

%

199.9 100.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00801 | L_MPot_1: Lower limit

Data type: INTEGER_16

Index: 23774

d

= 5CDE

h

FB

L_MPot_1

: Lower limit of the motor potentiometer function

Setting range

(min. value | unit | max. value)

Lenze setting

-199.9

%

199.9 -100.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Advertising