3 parameterise drive/application, Parameterise drive/application, 3commissioning – Lenze 8400 BaseLine D User Manual

Page 34

Advertising
background image

3

Commissioning

3.4

Commissioning with the »Engineer«

34

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.4.3

Parameterise drive/application

Go to Workspace and change to the Application parameters tab.

Parameterising the motor control
On the left, the parameters of the motor control are arranged:

1. Go to the Motor control (

C006

) list field and select the required motor control.

Note!

In the Lenze setting, the V/f characteristic control (VFCplus) with linear characteristic is

set in

C006

as motor control.

• The V/f characteristic control (VFCplus) is an motor control for standard frequency in-

verter applications based on a simple and robust control process which is suitable for

the operation of machines with linear or square-law load torque characteristic (e.g.

fans).

• The parameter settings have been set in advance in such a way that, if the drive con-

troller and 50 Hz asynchronous machine match each other in terms of performance,

the drive controller is immediately ready for operation without any further parameter

setting work and the motor works satisfactorily.

Advertising