Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

105

5

Motor control (MCTRL)

5.8

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.8.2

Motor load monitoring (I2xt)

The Inverter Drives 8400 are provided with a simple, sensorless, thermal I

2

xt motor monitoring of

self-ventilated standard motors which is based on a mathematical model.

• In

C066

displays the calculated motor load in [%]..

• If the motor load reaches the switch-off threshold set in

C120

:

• The error response set in

C606

will be carried out (Lenze setting: "Warning").

• The "

OC6: I2xt motor overload

" error message will be entered into the logbook.

• A setting of

C606

= "0: No Reaction" deactivates the monitoring.

Adjustment of the motor utilisation meter
The motor utilisation meter for indicating the motor load in

C066

begins to count when the appa-

rent motor current (

C054

) is greater than the set overload threshold (

C120

).

The overload threshold (

C120

) is to be set as follows:

• If you reduce

C120

starting from the calculated value, the motor utilisation meter will already

be counted up before the rated overload threshold is reached.

• If you reduce

C120

starting from the calculated value, the motor utilisation meter will already

be counted up before the rated overload threshold is reached.

Stop!

The I

2

xt motor monitoring does not present full motor protection! As the motor utilisa-

tion calculated in the thermal motor model is lost after mains switching, for instance the

following operating states cannot be measured correctly:

• Restarting (after mains switching) of a motor that is already very hot.
• Change of the cooling conditions (e.g. cooling air flow interrupted or too warm).

A full motor protection requires additional measures as e.g. the evaluation of tempera-

ture sensors that are located directly in the winding or the use of thermal contacts.

Note!

From version 03.04.00

, the thermal motor load displayed in

C066

can be pre-initialised

when the device is connected to the mains, optionally using a fixed value or the value

used last at the time when the device was switched off. The desired initialisation is se-

lected in

C122

. In the Lenze setting of

C122

, the behaviour remains unchanged (no initi-

alisation).

I

r

: Rated motor current (see nameplate of motor)

I

N

: Rated controller current at a switching frequency of f = 8 kHz

C00120

I

r

I

N

-----

100%

=