5 enable controller and select speed, Save parameter settings safe against mains failure, Enable controller and select speed – Lenze 8400 BaseLine D User Manual

Page 38: 3commissioning

Advertising
background image

3

Commissioning

3.4

Commissioning with the »Engineer«

38

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.4.4

Save parameter settings safe against mains failure

In order that parameter settings made in the device do not get lost by means of mains switching,

you must safe the parameter set explicitly safe against mains failure in the device.

Save parameter set

3.4.5

Enable controller and select speed

When the controller is in the "

SwitchedON

" state:

1. Enable controller:

Set terminal X4/RFR to HIGH level or close contact to terminal X4/12I n.

2. Select speed:

• In the "Terminals 0" by selecting a voltage at the analog input or by selecting a fixed setpoint

via the digital inputs DI1/DI2.

Tip!
More control functions in the "Terminals 0" control mode:

• DI3: HIGH level ≡ request DC-injection braking
• DI4: HIGH level ≡ request change of direction of rotation

Note!

If the controller is enabled at power-on and the auto-start option is activated in

C142

(Lenze setting), the controller remains in the "

ReadyToSwitchON

" state (display in

C137

).

For changing to the "

SwitchedON

" state, first deactivate the controller enable: Set termi-

nal X4/RFR to LOW level or open contact to terminal X4/12I.

DI1

DI2

Speed selection

LOW

LOW

The setpoint speed is selected via the analog input 1

• Scaling: 10 V ≡ 100 % ≡ reference speed (

C011

)

HIGH

LOW

The fixed setpoint 1 (

C039/1

) is used as setpoint speed.

• Lenze setting: 40 % of the reference speed (

C011

)

LOW

HIGH

The fixed setpoint 2 (

C039/2

) is used as setpoint speed.

• Lenze setting: 60 % of the reference speed (

C011

)

HIGH

HIGH

The fixed setpoint 3 (

C039/3

) is used as setpoint speed.

• Lenze setting: 80 % of the reference speed (

C011

)

Note!

Observe the actual speed value (display in

C051

) as well as the

LED status display

and

Display messages

indicated in the keypad.