Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

177

9

Parameter reference

9.2

Parameter list | C00021

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00021

C00022

C00023

C00024

Parameter | Name:

C00021 | Slip comp.

Data type: INTEGER_16

Index: 24554

d

= 5FEA

h

Slip compensation for V/f characteristic control (

VFCplus

) and sensorless vector control (

SLVC

)

• An increase of the slip compensation causes a greater frequency and voltage increase when the machine is loa-

ded.

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered auto-

matically. An automatic detection via the motor parameter identification is possible as well.

Motor control (MCTRL)

:

Optimising the operational performance by slip compensation

Setting range

(min. value | unit | max. value)

Lenze setting

-50.00

%

50.00 0.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00022 | Imax in motor mode

Data type: UNSIGNED_16

Index: 24553

d

= 5FE9

h

Maximum current in motor mode for all motor control modes
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A

99.99 47.00 A

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00023 | Imax in generator mode

Data type: INTEGER_16

Index: 24552

d

= 5FE8

h

Maximum current in generator mode for all motor control modes

• 100 % ≡ Imax in motor mode (

C00022

)

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

100.0 100.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00024 | Comparison value N_Act

Data type: INTEGER_16

Index: 24551

d

= 5FE7

h

Threshold for the actual speed comparison

• This parameter serves to set a threshold that is compared with the actual speed value.

• When the value falls below this threshold, the bNactCompare output of the SB

LS_DriveInterface

switches to

TRUE.

• Switching hysteresis = +1 %

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

199.9 0.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100