6 parameterisable additional functions, 1 selection of switching frequency, Parameterisable additional functions – Lenze 8400 BaseLine D User Manual

Page 93: Selection of switching frequency, Chapter, 5motor control (mctrl)

Advertising
background image

Lenze · 8400 BaseLine D · Reference manual · DMS 5.5 EN · 01/2014 · TD05

93

5

Motor control (MCTRL)

5.6

Parameterisable additional functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.6

Parameterisable additional functions

5.6.1

Selection of switching frequency

The switching frequency of the inverter that can be selected in

C018

influences the smooth running

performance and the noise generation in the connected motor as well as the power losses in the

controller.
The lower the switching frequency the higher the concentricity factor, the smaller the losses, and

the higher the noise generation.

Settable switching frequencies

Tip!
The Lenze setting

C018

= 2 (8 kHz var./drive-opt.) is the optimal value for standard applica-

tions.

Stop!

If operated at a switching frequency of 16 kHz, the output current of the controller must

not exceed the current limit values specified in the technical data!

Defining current and speed limits

( 77)

Note!

• Operate mid-frequency motors only at a switching frequency of 8 kHz or 16 kHz

(var./drive-opt.).

• If operated at a switching frequency of 16 kHz, the Ixt evaluation (

C064

) is considered

including the required derating to 67 % of the rated device current at switching fre-

quencies of 2.4 and 8 kHz.

Selection in

C018

Info

1 4 kHz var./drive-optimised

• "var.": Adaptation of the switching frequency depending on the

current

• "drive-opt.": drive-optimised modulation ("sine/delta modulati-

on")

• "fixed": fixed switching frequencies

2 8 kHz var./drive-optimised
3 16 kHz var./drive-optimised
5 2 kHz constant/drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised

21 8 kHz var./drive-opt./4 kHz min
22 16 kHz var./drive-opt./4 kHz min
23 16 kHz var./drive-opt./8 kHz min

Advertising